Electrical data | |
---|---|
Category IEC / EN / VDE | Class II / Type 2 / C |
Max. continuous operating voltage (AC/DC) Uc (L-N) | 385/500 V |
Max. continuous operating voltage (AC/DC) Uc (N-PE) | – |
Nominal discharge current (8/20) In | 20 kA per pole |
Max. discharge current (8/20) Imax | 40 kA per pole |
Voltage protection level Up (L-N) | < 1.9 kV |
Voltage protection level Up (N-PE) | – |
Residual voltage Ures @ 5kA(8/20) | < 1.4 kV |
Follow current Ifi | NO |
Response time tA | < 25 ns |
Thermal protection | YES |
Back-up fuse (if mains > 250 A) | 125 Agl |
Short-circuit withstand ISCCR | 25 kA/50 Hz |
General Data | |
Operating temperature | -40 ~ 80℃ |
Terminal screw torque | max. 3.0 Nm |
Terminal cross section | 35 mm2 (solid) / 25 mm2 (stranded) |
Mounting | 35 mm DIN rail, EN 60715 |
Protection degree | IP20 |
Housing material | Thermoplastic; inflammability class UL 94 V-0 |
Indication of disconnector operation | red flag |
Remote contacts (RC) | YES |
Remote contact ratings | AC: 250 V/0.5 A, 125 V/3 A |
Remote terminal cross section | max. 1.5 mm2 |
Remote terminal torque | 0.25 Nm |
Standard | IEC/EN 61643-11 |
Network systems | TN-S |
Protection mode | L/N-PE |